{"id":5286,"date":"2025-09-01T00:00:00","date_gmt":"2025-09-01T00:00:00","guid":{"rendered":"https:\/\/lp.szlogic.cn\/knowledge-center\/insertion-loss-vs-return-loss-in-optical-transceivers\/"},"modified":"2026-06-22T07:58:55","modified_gmt":"2026-06-22T07:58:55","slug":"insertion-loss-vs-return-loss-in-optical-transceivers","status":"publish","type":"post","link":"https:\/\/resourceslp.szlogic.cn\/id\/knowledge-center\/insertion-loss-vs-return-loss-in-optical-transceivers","title":{"rendered":"Perbedaan Utama antara Insertion Loss dan Return Loss pada Modul Optik"},"content":{"rendered":"<figure class=\"wp-block-image aligncenter size-large\"><img fetchpriority=\"high\" decoding=\"async\" width=\"1200\" height=\"712\" src=\"https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/27210832f30b44789c72aeac7018c07c.webp\" alt=\"Return Loss vs. Insertion Loss  \" class=\"wp-image-5281\" srcset=\"https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/27210832f30b44789c72aeac7018c07c.webp 1200w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/27210832f30b44789c72aeac7018c07c-300x178.webp 300w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/27210832f30b44789c72aeac7018c07c-1024x608.webp 1024w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/27210832f30b44789c72aeac7018c07c-768x456.webp 768w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/27210832f30b44789c72aeac7018c07c-18x12.webp 18w\" sizes=\"(max-width: 1200px) 100vw, 1200px\" \/><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\" >Pendahuluan<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Dalam jaringan serat optik,<br>, <a target=\"_blank\" rel=\"\" href=\"https:\/\/resourceslp.szlogic.cn\/id\/knowledge-center\/optical-transceiver-insertion-loss-definition-impact\/\"><strong>kerugian masukan (IL)<\/strong><\/a> and <a target=\"_blank\" rel=\"\" href=\"https:\/\/resourceslp.szlogic.cn\/id\/knowledge-center\/optical-transceiver-return-loss-back-reflection-guide\/\"><strong>return loss (RL)<br><\/strong><\/a> adalah dua metrik kritis yang harus dipahami oleh setiap insinyur. Sementara IL mengukur seberapa banyak daya optik hilang saat melewati suatu komponen, RL mengukur seberapa banyak daya yang dipantulkan kembali ke arah pemancar. Keduanya memengaruhi kinerja jaringan, tetapi dengan cara yang berbeda.<br>.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Memilih komponen, konektor, dan transceiver yang tepat bergantung pada pemahaman perbedaan-perbedaan ini. Artikel ini membandingkan insertion loss dan return loss, menjelaskan kapan masing-masing menjadi penting, serta memberikan panduan praktis untuk penerapan<br> <a target=\"_blank\" rel=\"\" href=\"https:\/\/www.l-p.com\/store-25432-optics-transceivers-sfp-modules.htm\"><strong>Modul optik LINK-PP<\/strong><\/a>.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" >Memahami Insertion Loss<br><\/h2>\n\n\n\n<h3 class=\"wp-block-heading\" >1 Definisi<br><\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Insertion loss mengkuantifikasi<br> <strong>pengurangan daya optik<br><\/strong> antara input dan output suatu perangkat atau tautan serat.<br>.<\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-large\"><img decoding=\"async\" width=\"1200\" height=\"320\" src=\"https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/73971f35547f49cca0e23d6f0a38e9a3.webp\" alt=\"What is Insertion Loss\uff1f\" class=\"wp-image-5282\" srcset=\"https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/73971f35547f49cca0e23d6f0a38e9a3.webp 1200w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/73971f35547f49cca0e23d6f0a38e9a3-300x80.webp 300w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/73971f35547f49cca0e23d6f0a38e9a3-1024x273.webp 1024w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/73971f35547f49cca0e23d6f0a38e9a3-768x205.webp 768w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/73971f35547f49cca0e23d6f0a38e9a3-18x5.webp 18w\" sizes=\"(max-width: 1200px) 100vw, 1200px\" \/><\/figure>\n\n\n\n<ul class=\"wp-block-list\">\n<li><p>IL yang lebih rendah lebih baik; artinya lebih banyak cahaya mencapai penerima.<br>.<\/p><\/li><li><p>Penyebab umum meliputi kehilangan pada konektor, atenuasi serat, sambungan (splices), dan kelengkungan.<br>.<\/p><\/li>\n<\/ul>\n\n\n\n<h3 class=\"wp-block-heading\" >2 Mengapa IL Penting<br><\/h3>\n\n\n\n<ul class=\"wp-block-list\">\n<li><p>Secara langsung mengurangi daya yang diterima dan margin tautan.<br>.<\/p><\/li><li><p>IL tinggi dapat menyebabkan kesalahan bit atau kegagalan tautan jika daya yang diterima berada di bawah sensitivitas penerima.<br>.<\/p><\/li><li><p>Sangat kritis untuk tautan jarak jauh atau tautan dengan anggaran terbatas.<br>.<\/p><\/li>\n<\/ul>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Contoh:<\/strong><br\/>Sebuah tautan mode-tunggal sepanjang 10 km dengan dua konektor dan satu sambungan dapat memiliki IL \u2248 2,4 dB. Jika daya pemancar dikurangi IL berada di bawah sensitivitas penerima, maka tautan gagal.<br>.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" >Memahami Return Loss<br><\/h2>\n\n\n\n<h3 class=\"wp-block-heading\" >1 Definisi<br><\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Return loss mengukur<br> <strong>jumlah daya optik yang dipantulkan kembali<br><\/strong> ke arah pemancar:<br><\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-large\"><img decoding=\"async\" width=\"1200\" height=\"320\" src=\"https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/0c918d26f4554479853206e3465ce778.webp\" alt=\"What is Return Loss\uff1f\" class=\"wp-image-5283\" srcset=\"https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/0c918d26f4554479853206e3465ce778.webp 1200w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/0c918d26f4554479853206e3465ce778-300x80.webp 300w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/0c918d26f4554479853206e3465ce778-1024x273.webp 1024w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/0c918d26f4554479853206e3465ce778-768x205.webp 768w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/0c918d26f4554479853206e3465ce778-18x5.webp 18w\" sizes=\"(max-width: 1200px) 100vw, 1200px\" \/><\/figure>\n\n\n\n<ul class=\"wp-block-list\">\n<li><p>RL yang lebih tinggi (lebih banyak dB) = pantulan lebih sedikit = lebih baik.<br>.<\/p><\/li><li><p>RL melindungi laser dari cahaya yang dipantulkan balik, yang dapat menstabilkan sumber.<br>.<\/p><\/li>\n<\/ul>\n\n\n\n<h3 class=\"wp-block-heading\" >2 Mengapa RL Penting<br><\/h3>\n\n\n\n<ul class=\"wp-block-list\">\n<li><p>RL rendah (pantulan tinggi) dapat menyebabkan<br> <strong>laser mode hopping, noise intensitas, dan peningkatan BER<br><\/strong>.<\/p><\/li><li><p>Terutama penting untuk DWDM, RF-analog-over-fiber, dan transceiver jarak jauh yang sensitif.<br>.<\/p><\/li>\n<\/ul>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Nilai RL konektor khas:<br><\/strong><\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><p>PC: ~40 dB<br><\/p><\/li><li><p>UPC: ~50 dB<br><\/p><\/li><li><p>APC: ~60 dB atau lebih tinggi<br><\/p><\/li>\n<\/ul>\n\n\n\n<h2 class=\"wp-block-heading\" >Perbandingan Insertion Loss dan Return Loss: Perbedaan Utama<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Anda perlu memahami perbedaan antara return loss dan insertion loss. Keduanya memengaruhi jaringan serat optik Anda, tetapi mengukur hal yang berbeda. Return loss mengukur jumlah sinyal yang dipantulkan, sedangkan insertion loss mengukur kehilangan sinyal maju saat melewati suatu komponen.<\/p>\n\n\n\n<figure class=\"wp-block-table\">\n<table class=\"has-fixed-layout\">\n<colgroup><col style=\"width: 151px;\"\/><col style=\"min-width: 25px;\"\/><col style=\"min-width: 25px;\"\/><\/colgroup><tbody><tr><th colspan=\"1\" rowspan=\"1\" colwidth=\"151\"><p>Fitur<\/p><\/th><th colspan=\"1\" rowspan=\"1\"><p>Rugi Masukan (IL)<\/p><\/th><th colspan=\"1\" rowspan=\"1\"><p>Return Loss (RL)<\/p><\/th><\/tr><tr><td colspan=\"1\" rowspan=\"1\" colwidth=\"151\"><p>Definisi<\/p><\/td><td colspan=\"1\" rowspan=\"1\"><p>Kehilangan daya maju<\/p><\/td><td colspan=\"1\" rowspan=\"1\"><p>Daya pantul balik<\/p><\/td><\/tr><tr><td colspan=\"1\" rowspan=\"1\" colwidth=\"151\"><p>Satuan<\/p><\/td><td colspan=\"1\" rowspan=\"1\"><p>dB (semakin kecil semakin baik)<\/p><\/td><td colspan=\"1\" rowspan=\"1\"><p>dB (semakin besar semakin baik)<\/p><\/td><\/tr><tr><td colspan=\"1\" rowspan=\"1\" colwidth=\"151\"><p>Dampak<\/p><\/td><td colspan=\"1\" rowspan=\"1\"><p>Mengurangi daya penerimaan &amp; margin<\/p><\/td><td colspan=\"1\" rowspan=\"1\"><p>Mempengaruhi stabilitas laser &amp; BER<\/p><\/td><\/tr><tr><td colspan=\"1\" rowspan=\"1\" colwidth=\"151\"><p>Pengukuran<\/p><\/td><td colspan=\"1\" rowspan=\"1\"><p>OLTS, meter daya<\/p><\/td><td colspan=\"1\" rowspan=\"1\"><p>Meter ORL, OTDR<\/p><\/td><\/tr><tr><td colspan=\"1\" rowspan=\"1\" colwidth=\"151\"><p>Penting Untuk<\/p><\/td><td colspan=\"1\" rowspan=\"1\"><p>Tautan panjang, jalur multi-konektor<\/p><\/td><td colspan=\"1\" rowspan=\"1\"><p>Tautan sensitif terhadap laser, analog, DWDM<\/p><\/td><\/tr><\/tbody>\n<\/table>\n<\/figure>\n\n\n\n<blockquote class=\"wp-block-quote is-layout-flow wp-block-quote-is-layout-flow\"><p><strong>Wawasan Utama:<\/strong> IL dan RL adalah metrik independen\u2014suatu komponen dapat memiliki IL rendah tetapi RL buruk, dan sebaliknya. Keduanya harus memenuhi persyaratan sistem.<\/p><\/blockquote>\n\n\n\n<h3 class=\"wp-block-heading\" >Langkah-Langkah Pengujian Insertion Loss:<\/h3>\n\n\n\n<ol class=\"wp-block-list\" >\n<li><p>Acukan daya tanpa Device Under Test (DUT).<\/p><\/li><li><p>Masukkan DUT.<\/p><\/li><li><p>Ukur kehilangan daya.<\/p><\/li><li><p>Terapkan rumus IL.<\/p><\/li>\n<\/ol>\n\n\n\n<h3 class=\"wp-block-heading\" >Langkah-Langkah Pengujian Return Loss:<\/h3>\n\n\n\n<ol class=\"wp-block-list\" >\n<li><p>Injeksikan cahaya ke dalam DUT.<\/p><\/li><li><p>Ukur daya pantul.<\/p><\/li><li><p>Gunakan rumus RL.<\/p><\/li>\n<\/ol>\n\n\n\n<p class=\"wp-block-paragraph\">Anda mungkin bertanya-tanya bagaimana cara menguji return loss di jaringan Anda. Prosedur pengujian return loss menggunakan instrumen khusus untuk mengukur reflektansi dan kehilangan pada setiap titik koneksi. Mengujikan return loss dan insertion loss secara bersamaan memberi Anda gambaran lengkap tentang kesehatan jaringan Anda. Sebagai contoh, <a target=\"_blank\" rel=\"\" href=\"https:\/\/www.l-p.com\/products\/476132.htm\">transceiver SFP28 BIDI <\/a>mungkin memiliki rata-rata insertion loss sekitar 1,8 dB dan return loss kurang dari -12 dB. Nilai-nilai ini menunjukkan kemampuan perangkat dalam mempertahankan integritas sinyal pada jarak jauh. Nilai orl yang berbeda dapat menunjukkan seberapa baik jaringan Anda menangani reflektansi dan kehilangan.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Anda harus selalu memantau baik return loss maupun insertion loss. Pendekatan ini memastikan Anda mempertahankan kualitas sinyal tinggi dan kinerja jaringan yang andal.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" >Skenario Praktis<\/h2>\n\n\n\n<h3 class=\"wp-block-heading\" >1 Skenario 1: Tautan Data Center Jarak Dekat<\/h3>\n\n\n\n<ul class=\"wp-block-list\">\n<li><p>IL biasanya lebih penting.<\/p><\/li><li><p>Efek pantulan minimal untuk penerima digital yang andal.<\/p><\/li><li><p>Contoh: Penerapan <a target=\"_blank\" rel=\"\" href=\"https:\/\/www.l-p.com\/products\/475829.htm\"><strong>LINK-PP LS-SW3110-02C<\/strong><\/a> dalam tautan 10G sepanjang 2 km dengan banyak konektor. Memastikan IL  26 dB sudah cukup.<\/p><\/li>\n<\/ul>\n\n\n\n<h3 class=\"wp-block-heading\" >2 Skenario 2: Jaringan Jangkauan Jauh atau DWDM<\/h3>\n\n\n\n<ul class=\"wp-block-list\">\n<li><p>RL menjadi kritis. Laser berkecepatan tinggi (DFB\/FP) sensitif terhadap pantulan.<\/p><\/li><li><p>Contoh: tautan DWDM 40 km dengan konektor APC dan <a target=\"_blank\" rel=\"\" href=\"https:\/\/www.l-p.com\/products\/476095.htm\"><strong>modul LINK-PP SFP28 25G<\/strong><\/a>. Pantulan rendah (RL \u2265 60 dB) memastikan operasi laser yang stabil dan BER rendah.<\/p><\/li>\n<\/ul>\n\n\n\n<h3 class=\"wp-block-heading\" >3 Skenario 3: Lingkungan Campuran<\/h3>\n\n\n\n<ul class=\"wp-block-list\">\n<li><p>Baik IL maupun RL penting: IL untuk anggaran, RL untuk perlindungan laser.<\/p><\/li><li><p>Insinyur harus mengukur IL menggunakan OLTS dan RL menggunakan meter ORL, lalu membandingkannya dengan spesifikasi lembar data modul.<\/p><\/li>\n<\/ul>\n\n\n\n<h2 class=\"wp-block-heading\" >Panduan Transceiver LINK-PP<\/h2>\n\n\n\n<figure class=\"wp-block-image aligncenter size-large\"><img loading=\"lazy\" decoding=\"async\" width=\"1200\" height=\"675\" src=\"https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/e37288a1fe01456d9ee6696871e880fe.jpg\" alt=\"LINK-PP Optical Transceiver\" class=\"wp-image-5284\" srcset=\"https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/e37288a1fe01456d9ee6696871e880fe.jpg 1200w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/e37288a1fe01456d9ee6696871e880fe-300x169.jpg 300w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/e37288a1fe01456d9ee6696871e880fe-1024x576.jpg 1024w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/e37288a1fe01456d9ee6696871e880fe-768x432.jpg 768w, https:\/\/resourceslp.szlogic.cn\/wp-content\/uploads\/2026\/05\/e37288a1fe01456d9ee6696871e880fe-18x10.jpg 18w\" sizes=\"(max-width: 1200px) 100vw, 1200px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">Modul LINK-PP dirancang untuk memberikan kinerja IL dan RL yang konsisten. Contohnya meliputi:<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><p><a target=\"_blank\" rel=\"\" href=\"https:\/\/www.l-p.com\/products\/475605.htm\"><strong>SFP+ LR 10G<\/strong><\/a>: IL &lt; 0,5 dB, RL \u2265 30 dB<\/p><\/li><li><p><a target=\"_blank\" rel=\"\" href=\"https:\/\/www.l-p.com\/products\/476046.htm\"><strong>25G SFP28 LR<\/strong><\/a>: Mendukung penerapan berkehilangan rendah dan berpantulan rendah untuk pusat data<\/p><\/li>\n<\/ul>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Tips Teknis:<\/strong> Selalu tinjau lembar data untuk nilai IL dan RL sebelum penerapan, terutama jika melibatkan banyak konektor atau jarak jauh.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" >Praktik Terbaik untuk Penerapan Jaringan<\/h2>\n\n\n\n<ol class=\"wp-block-list\" >\n<li><p><a target=\"_blank\" rel=\"\" href=\"https:\/\/resourceslp.szlogic.cn\/id\/knowledge-center\/pc-vs-upc-vs-apc-fiber-connector-comparison-guide\/\"><strong>Pilih jenis konektor yang tepat<\/strong><\/a><strong>:<\/strong> APC untuk tautan yang sensitif terhadap pantulan; UPC\/PC untuk Ethernet digital standar.<\/p><\/li><li><p><strong>Hitung anggaran tautan:<\/strong> Sertakan seluruh IL dari konektor, sambungan, dan atenuasi serat.<\/p><\/li><li><p><strong>Uji kedua parameter:<\/strong> OLTS untuk IL, meter ORL untuk RL.<\/p><\/li><li><p><strong>Bersihkan dan inspeksi konektor:<\/strong> Kotoran dan goresan meningkatkan baik IL maupun pantulan.<\/p><\/li><li><p><strong>Dokumentasikan nilai dasar:<\/strong> Berguna untuk pemecahan masalah dan perawatan.<\/p><\/li>\n<\/ol>\n\n\n\n<h2 class=\"wp-block-heading\" >FAQ<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Q1:<\/strong> Apakah suatu modul dapat memiliki IL rendah tetapi RL buruk?<br\/><strong>A:<\/strong> Ya. Suatu komponen mungkin mentransmisikan cahaya secara efisien (IL rendah) tetapi memantulkan kembali terlalu banyak (RL buruk), sehingga memengaruhi stabilitas laser.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Q2:<\/strong> Metrik mana yang lebih penting?<br\/><strong>A:<\/strong> Hal ini tergantung pada aplikasi. Tautan digital jarak pendek memprioritaskan IL, sedangkan jaringan yang sensitif terhadap laser atau jarak jauh memprioritaskan RL.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Q3:<\/strong> Seberapa sering saya harus menguji IL dan RL?<br\/><strong>A:<\/strong> Saat pemasangan dan setelah setiap pemeliharaan besar. Tautan dengan kritisitas tinggi mungkin memerlukan pengujian ulang secara berkala.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\" >Kesimpulan<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Memahami baik insertion loss (IL) maupun return loss (RL) sangat penting untuk merancang, menyebarluaskan, dan memelihara jaringan optik berkinerja tinggi. IL memengaruhi daya yang diterima dan margin tautan, sedangkan RL melindungi stabilitas laser dan mengurangi BER.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Bagi insinyur yang menerapkan <a target=\"_blank\" rel=\"\" href=\"https:\/\/www.l-p.com\/store-25432-optics-transceivers-sfp-modules.htm\"><strong>Modul optik LINK-PP<\/strong><\/a>, memeriksa kedua IL dan RL memastikan tautan yang andal dan berkecepatan tinggi dengan kinerja yang dapat diprediksi. Dengan menggabungkan desain yang tepat, pengukuran, dan pemeliharaan, operator dapat mencapai efisiensi jaringan optimal serta umur pakai yang panjang.<\/p>","protected":false},"excerpt":{"rendered":"<p>Pelajari perbedaan antara insertion loss dan return loss pada transceiver optik, dampaknya terhadap kinerja, metode pengukuran, serta panduan produk LINK-PP.<\/p>","protected":false},"author":1,"featured_media":5285,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[1],"tags":[26],"class_list":["post-5286","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-knowledge-center","tag-optics-transceivers"],"blocksy_meta":[],"acf":[],"_links":{"self":[{"href":"https:\/\/resourceslp.szlogic.cn\/id\/wp-json\/wp\/v2\/posts\/5286","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/resourceslp.szlogic.cn\/id\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/resourceslp.szlogic.cn\/id\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/resourceslp.szlogic.cn\/id\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/resourceslp.szlogic.cn\/id\/wp-json\/wp\/v2\/comments?post=5286"}],"version-history":[{"count":4,"href":"https:\/\/resourceslp.szlogic.cn\/id\/wp-json\/wp\/v2\/posts\/5286\/revisions"}],"predecessor-version":[{"id":11204,"href":"https:\/\/resourceslp.szlogic.cn\/id\/wp-json\/wp\/v2\/posts\/5286\/revisions\/11204"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/resourceslp.szlogic.cn\/id\/wp-json\/wp\/v2\/media\/5285"}],"wp:attachment":[{"href":"https:\/\/resourceslp.szlogic.cn\/id\/wp-json\/wp\/v2\/media?parent=5286"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/resourceslp.szlogic.cn\/id\/wp-json\/wp\/v2\/categories?post=5286"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/resourceslp.szlogic.cn\/id\/wp-json\/wp\/v2\/tags?post=5286"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}